An electric kettle consumes 1kW of electric power when operated at 220 V.a fuse.wire of what rating must be?

[From: ] [author: ] [Date: 14-02-16] [Hit: ]
......
Used for it?
1A
2A
4A
5A

-
P = V*I => 1kW = 1000W = 220*i => 1000W/220V = i = 100/22 = 50/11 = 4.55A so the answer is 5A

-
6A

Current consumed is 1000/220 = 4.54A. 133% of that is 6.06

RERATING: For 25ºC ambient temperatures, it is
recommended that fuses be operated at no more than
75% of the nominal current rating