Solve this problem: a chiller is rated 1500TR and has an efficiency of 0.65kw/TR, What is the Condenser Heat R
Favorites|Homepage
Subscriptions | sitemap
HOME > Engineering > Solve this problem: a chiller is rated 1500TR and has an efficiency of 0.65kw/TR, What is the Condenser Heat R

Solve this problem: a chiller is rated 1500TR and has an efficiency of 0.65kw/TR, What is the Condenser Heat R

[From: ] [author: ] [Date: 11-05-24] [Hit: ]
......
Qc = [(COP + 1) / COP] Qe
Qe = 1500TR = 5280 kW
COP = 3.52 / 0.65kw/TR = 5.415

Therefore: Qc = 6255kW or 1777 TR
1
keywords: the,efficiency,of,1500,is,this,and,Condenser,rated,What,kw,problem,Solve,chiller,an,0.65,TR,Heat,has,Solve this problem: a chiller is rated 1500TR and has an efficiency of 0.65kw/TR, What is the Condenser Heat R